制冷剂有限时间泄漏扩散模型 预览 被引量:3

Finite-Time Diffusion Models of Leaked Refrigerant
在线阅读 下载PDF
收藏 分享 导出
摘要 针对高斯模型不能计算有限时间泄漏扩散场浓度的缺陷,研究并得到了储罐系统制冷剂泄漏时质量泄漏速度与时间的关系式,建立了制冷剂一维、三维扩散数学物理模型,通过求解模型解析解和数值解,解决了制冷剂储罐有限时间泄漏扩散的浓度分布问题,比较了点源有限时间泄漏扩散模型和高斯烟雨模型的精度,结果表明,前者更能反映泄漏制冷剂的实际扩散过程. To solve the problem that the Gaussian model could not calculate the concentration of finite-time diffusion, this paper obtained the relations between the mass leakage velocity of refrigerants and time when leakages happened to a tank. One-dimensional and three-dimensional physical and mathematical diffusion models of refrigerants were put forward. The concentration of refrigerants after finite-time release and diffusion was gained through the numerical and analytical solutions of the model. The precision of Gaussian model was compared with that of the model put forward in this paper. And the calculated results showed that the latter described the actual diffusion duration better than the former.
作者 杨昭 彭继军 张甫仁 YANG Zhao, PENG Ji-jun, ZHANG Fu-ren (School of Mechanical Engineering, Tianjin University, Tianjin 300072 ,China)
出处 《天津大学学报》 EI CAS CSCD 北大核心 2006年第6期 657-662,共6页 Journal of Tianjin University(Science and Technology)
基金 国家自然科学基金资助项目(50376048) 教育部博士点基金资助项目(20030056027).
关键词 制冷剂 泄漏 扩散 数学模型 解析解 refrigerant leakage diffuse mathematical model analytical solution
作者简介 杨昭(1960-),女,博士,教授,zhaoyang@tju.edu.cn. 联系人:彭继军,jijun-78@163.com.
  • 相关文献

参考文献10

二级参考文献36

共引文献71

同被引文献30

  • 1吴晋湘 ,张丽娟 ,刘立辉 ,贾云飞 ,苗青 .室内可燃气体泄漏后浓度场变化的实验研究[J].消防科学与技术,2005,24(2):169-171. 被引量:13
  • 2杨昭,彭继军,张甫仁.纯制冷剂贮罐外泄动态过程分析[J].流体机械,2006,34(1):63-68. 被引量:3
  • 3于畅,田贯三.可燃气体室内泄漏扩散的研究[J].山东建筑工程学院学报,2006,21(3):243-247. 被引量:19
  • 4Atul S Padalkar, Kundlik V Mali, Sukumar Devotta. Simulated and experimental performance of split packaged air conditioner using refrigerant HC-290 as a substitute for HCFC-22 [J]. Applied Thermal Engineering, 2014, 62: 277-284. 被引量:1
  • 5Dalkilic A S, Wongwises S. A performance comparison of vapour-compression refrigeration system using various alternative refrigerants [J]. International Communications in Heat and Mass Transfer, 2010, 37: 1340-1349. 被引量:1
  • 6Devotta S, Waghmare A V, Sawant N N, Domkundwar B M. Alternatives to HCFC-22 for air conditioners [J]. Applied Thermal Engineering, 2001, 21: 703-715. 被引量:1
  • 7Li Tingxun(李廷勋), Liang Jierong(梁杰荣). Testing research on indoor R290 RAC leakage// 2010 China Household Electrical Appliances Technology Conference[C]. Hefei, 2010. 被引量:1
  • 8Li Tingxun. Indoor leakage test for safety of R-290 split type room air conditioner [J]. International Journal of Refrigeration, 2014, 40: 380-389. 被引量:1
  • 9Li Yunong, Tao Junjun, Han Yuchong, Han Xue, Qin Jun. Numerical and experimental study on the diffusion property of difluoromethane (HFC-32) in leakage [J]. Procedia Engineering, 2014, (71): 34-43. 被引量:1
  • 10Colbourne D, Suen K O. Appraising the flammability hazards of hydrocarbon refrigerants using quantitative risk assessment model(Ⅰ): Modelling approach [J]. International Journal of Refrigeration, 2004, 27: 774-783. 被引量:1